FAULT CODE =  403
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Comms fault between boards - check inverter error detail for which 2 boards, check transformer, bus voltage and inter-connecting cables

FAULT CODE = 900
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Lossnay unit in test run

FAULT CODE = 1102
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = High compressor discharge temperature. Discharge temperature has exceeded 110°C or more. Short of refrigerant. Discharge thermistor

FAULT CODE = 1111
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Low pressure/temperature fault - check thermistors (TH2, TH3, TH4), gas charge, indoor fan, heat exchanger and filter

FAULT CODE = 1112
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Low pressure/temperature fault - check thermistors (TH2, TH3, TH4), gas charge, indoor fan, heat exchanger and filter

FAULT CODE = 1113
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Low pressure/temperature fault - check thermistors (TH2, TH3, TH4), gas charge, indoor fan, heat exchanger and filter

FAULT CODE = 1202
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary fault to 1102

FAULT CODE = 1204
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary heat exchanger gas temperature sensor fault - check thermistors 10a and 10b

FAULT CODE = 1205
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH5)

FAULT CODE = 1211
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH2)

FAULT CODE =  1214
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (THHS)

FAULT CODE = 1216
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH7)

FAULT CODE = 1217
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH8)

FAULT CODE = 1219
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH9)

FAULT CODE = 1221
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH6)

FAULT CODE = 1243
R22 = -
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Preliminary thermistor fault (TH10)

FAULT CODE = 1301
R22 = -
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Low pressure fault (63L operation) low pressure sensor sensing less than 1 bar immediately before starting

FAULT CODE = 1302
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = High pressure fault - check pressure in system for more than 29 bar (R407c) 38 bar (R410A). Check high pressure sensor against gauge pressure

FAULT CODE = 1368
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Pressure sensor fault (PS1) at BC - compare pressure reading on SW1 on O/C

FAULT CODE = 1370
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Pressure sensor fault (PS3) at BC - compare pressure reading on SW1 at O/C

FAULT CODE = 1402
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary fault to 1302

FAULT CODE = 1500
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = System overcharge. Abnormal low compressor superheat - discharge thermistor TH4

FAULT CODE = 1501
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = High compressor shell temp - check for shortage of gas, insufficient indoor index running (comms room units)

FAULT CODE = 1505
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Suction pressure abnormal - generated by low pressure sensor detecting a vacuum - check for blockage, closed valve or sensor fault

FAULT CODE = 2500
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Detecting lack of water flow on a water circuit

FAULT CODE = 2502
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = I/C has water level in drip tray, when the unit was running in cooling (temperature sensors - check for open or closed circuit and operation of pump)

FAULT CODE = 2503
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = I/C has water level in drip tray when the unit was running in cooling (float sensor - check for closed circuit on float switch and operation of pump)

FAULT CODE = 2600
R22 = x
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Water leak from humidifier

FAULT CODE = 4100
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Compressor over current protection on Mr Slim with M-net interface - check inverter or compressor

FAULT CODE = 4101
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Compressor over current protection on Mr Slim with M-net interface - check inverter or compressor

FAULT CODE = 4102
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Open phase fault - check power supply and noise filter for loss of phase, check wiring and fuses

FAULT CODE = 4103
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Reverse phase fault - check phase rotation, loss of phase through the noise filter, fuse blown and high pressure switch open at power on

FAULT CODE = 4106
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Transmission power supply fault - check wiring, high current, incorrect voltage on transmission line and/or M-Net board

FAULT CODE = 4108
R22 = -
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = Over current protection on DOL compressor - check power supply, contactor and compressor

FAULT CODE = 4115
R22 = x
R407c = x        
R410A = x                                                              
LOSSNAY = -
DESCRIPTION = Power supply abnormal - check power, fuses, connections and PCB

FAULT CODE = 4116
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Fan motor abnormal - check fan motor and board (relates to indoor unit or Lossnay unit)

FAULT CODE = 4124
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Thermal switch (49C) open circuit on Mr Slim on M-Net - reset and check pressures and air flow

FAULT CODE = 4210
R22 = x
R407c  = -
R410A = -
LOSSNAY = -
DESCRIPTION = Compressor over current problem - check inverter balance. Compressor and inverter

FAULT CODE = 4220
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Low inverter board BUS voltage. Less than 289VdcDC is detected. - check mains supply

FAULT CODE = 4225
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Low DC voltage on Vdc on fan inverter - check CNVdc for 300Vdc on diode stack and check mains power supply to outdoor unit

FAULT CODE = 4230
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = High temperature on heat sink on inverter - check for blockages in air duct, failure of INV fan or failure of thermistor

FAULT CODE = 4235
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Fan inverter heat sink overheat protection. Reduced airflow through heat sink. Fan motor problem. THHS thermistor problem.

FAULT CODE = 4240
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Over current protection. If high current is detected for more than 10 minutes - check inverter balance. Reduced airflow through heat sink

FAULT CODE = 4245
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Over current protection. Possible ACCT current sensor fault. Should read 280 ohms between pins 1 & 2 and across pins 3 & 4

FAULT CODE = 4250
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Over current protection. Inverter IPM problem. Compressor lock - check inverter balance

FAULT CODE = 4255
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Inverter cooling fan problem - if high static fan is used then check that SW3-9 is on

FAULT CODE = 4260
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Preliminary inverter heat sink overheat protection. Reduced airflow through heat sink. Fan motor problem. THHS thermistor problem.

FAULT CODE = 5101
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Thermistor fault at indoor/outdoor unit - check fault code address

FAULT CODE = 5102
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Thermistor fault at indoor/outdoor unit - check fault code address

FAULT CODE = 5103
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Thermistor fault at indoor/outdoor unit - check fault code address

FAULT CODE = 5104
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Thermistor fault at indoor/outdoor unit - check fault code address (indoor fault - check SW7-3 is off)

FAULT CODE = 5105
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = TH5 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5106
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = TH5 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5107
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = TH7 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5108
R22 = x
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = TH8 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5109
R22 = -
R407c = x
R410A = -
LOSSNAY = -
DESCRIPTION = TH9 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5110
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = TH10 open/short circuit - check if the TH is disconnected from the board

FAULT CODE = 5111
R22 = x
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH11 open/short circuit, disconnected from board/pipe

FAULT CODE = 5112
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH10 open/short circuit, disconnected from board/pipe

FAULT CODE = 5113
R22 = x
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH open/short circuit, disconnected from board/pipe

FAULT CODE = 5114
R22 = x
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH open/short circuit, disconnected from board/pipe

FAULT CODE = 5115
R22 = x
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH15 open/short circuit, disconnected from board/pipe

FAULT CODE = 5116
R22 = x
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = BC box thermistor error - TH16 open/short circuit, disconnected from board/pipe

FAULT CODE = 5201
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Pressure sensor fault outdoor unit/BC box - check fault code address/SW1 pressure sensor readings

FAULT CODE = 5202
R22 = x
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Pressure sensor fault (PS2) in the BC box

FAULT CODE = 5203
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Pressure sensor fault (PS3) in the BC box

FAULT CODE = 5300
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control UH fault - see Mr Slim fault code list

FAULT CODE = 5301
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Current sensor fault, ACCT or DCCT - check inv. error details

FAULT CODE = 5401
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Temperature sensor fault - check CN30 for humidity sensor

FAULT CODE = 5701
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Loose float switch connector - check switch, check CN4F on indoor unit

FAULT CODE = 6201
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = TB7 transmission line communication error - check for voltage abnormality/short

FAULT CODE = 6202
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Transmission processor hardware error - check for noise/short on M-Net cable

FAULT CODE = 6600
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Repeat address fault - two or more units are assigned the same address - correct the repeated address

FAULT CODE = 6601
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Polarity setting error - no voltage or short circuit on the m-net transmission line

FAULT CODE = 6602
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Hardware error of transmission processor. Noise interference. Polarity problem on TB7

FAULT CODE =
R22 =
R407c
R410A =
LOSSNAY = -
DESCRIPTION =

FAULT CODE = 6603
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Bus circuit busy - check if indoor unit, Lossnay unit or anything else has been wired into TB7, instead of TB3

FAULT CODE = 6607
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Communication issue - no response back from unit whilst system is operational

FAULT CODE = 6608
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Communication error - loss of voltage or noise entering the transmission line

FAULT CODE = 6700
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K control communication error - R22 type unit connected onto M-Net circuit comms error

FAULT CODE = 6701
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K control communication error - R22 type unit connected onto M-Net circuit comms error

FAULT CODE = 6702
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K control duplicate address error - two or more R22 type units connected onto M-Net circuit with the same address

FAULT CODE = 6750
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K control communication error - R22 type unit connected onto M-Net circuit comms error

FAULT CODE = 6751
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 R/A thermistor fault (P1)

FAULT CODE = 6752
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 frost protection at I/C (P6)

FAULT CODE = 6753
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Comms fault between O/C and I/C

FAULT CODE = 6754
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 drain fault (P5)

FAULT CODE = 6755
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 drain fault (P5)

FAULT CODE = 6756
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 frost protection at I/C (P6)

FAULT CODE = 6757
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = System error

FAULT CODE = 6758
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Comms fault between I/C and O/C

FAULT CODE = 6761
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 R/A thermistor fault (P1)

FAULT CODE = 6762
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 TH2 fault check resistance (P2)

FAULT CODE = 6763
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 Comms fault between I/C and O/C

FAULT CODE = 6764
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 drain fault (P4)

FAULT CODE = 6765
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 drain fault (P5)

FAULT CODE = 6766
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 frost protection at I/C (P6)

FAULT CODE = 6767
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = R22 comms fault between I/C and O/C

FAULT CODE = 6771
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - high pressure abnormality or low pressure abnormality

FAULT CODE = 6772
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - inner thermostat function, discharge temperature abnormality, shell thermostat function, over current protection

FAULT CODE = 6773
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - radiator plate thermostat function

FAULT CODE = 6774
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - outdoor thermistor abnormality

FAULT CODE = 6775
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - pressure sensor abnormality, indoor/outdoor communication error

FAULT CODE = 6776
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - over current shut-off

FAULT CODE = 6777
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - system error

FAULT CODE = 6778
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - normal

FAULT CODE = 6779
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = K abnormality - refrigerant overcharge, abnormal voltage, abnormal CT sensor

FAULT CODE = 6830
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = Comms fault between I/C and R/C check connections to MA R/C and check for 12Vdc check R/C not set sub controller

FAULT CODE = 6831
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = MA R/C communication fault - check connections on TB15 or that the controller was removed while the I/C was powered

FAULT CODE = 6832
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = MA controller comms fault - check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings

FAULT CODE = 6833
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = MA controller comms fault check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings

FAULT CODE = 6834
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = MA Controller comms fault - check cable length no bigger than 500m, check connection and type of cable used, check R/C not set sub on field settings

FAULT CODE = 6840
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control E6/E8 fault - see Mr Slim fault code list

FAULT CODE = 6841
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control E7/E9 fault - see Mr Slim fault code list

FAULT CODE = 6844
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control EA fault - see Mr Slim fault code list

FAULT CODE = 6845
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control Eb fault - see Mr Slim fault code list

FAULT CODE = 6846
R22 = -
R407c = -
R410A = -
LOSSNAY = -
DESCRIPTION = A-Control EC fault - see Mr Slim fault code list

FAULT CODE = 7100
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Over capacity - (R2 150% index exceeded) (Y 130% index exceeded)

FAULT CODE = 7101
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Capacity setting error - SW2 set wrong on indoors, SW5 on YHMA outdoor, (SW3-10 on older kit)

FAULT CODE = 7102
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Error in number of connected units - loss of M-Net voltage (short or break), no power to BC, wrong SW5 setting on box, wrong box type

FAULT CODE = 7105
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Address setting error - OC or BC addressed wrong

FAULT CODE = 7106
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Attribute setting error - SW3-1 setting on a GUF

FAULT CODE = 7107
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Port setting error - check if too much capacity on a single port, wiring SW2 setting, wrong SW14 setting or wrong units on a box when using multiple boxes

FAULT CODE = 7110
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Check SW5-7 is correctly set

FAULT CODE = 7111
R22 = x
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Remote control sensor fault - SW1 - 1 on and no controllers fitted or faulty remote controller

FAULT CODE = 7113
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Function setting error - wrong SW5 setting or wrong resistors fitted on YHM-A

FAULT CODE = 7117
R22 = -
R407c = -
R410A = x
LOSSNAY = -
DESCRIPTION = Model setting error - SW5 set wrong or wrong resistors in

FAULT CODE = 7130
R22 = -
R407c = x
R410A = x
LOSSNAY = -
DESCRIPTION = Incompatible equipment on M-Net - check split with MAC 399 wired onto the TB5 line TB5 line, not the TB7


Kindly Bookmark this Post using your favorite Bookmarking service:
Technorati Digg This Stumble Stumble Facebook Twitter

35 komentar:

Unknown on December 4, 2017 at 6:02 PM said...

if this post was likened to a flavor of yogurt, what flavor would it be? Banana, I think. browse around this site

Sreenivas on January 2, 2018 at 2:23 PM said...

I would like to thank you for the efforts you have made in writing this article. I am hoping the same best work from you in the future as well..
Mitsubishi Air Conditioner

Sreenivas on January 2, 2018 at 2:23 PM said...

I would like to thank you for the efforts you have made in writing this article. I am hoping the same best work from you in the future as well..
Mitsubishi Air Conditioner

dinowends on March 23, 2018 at 6:41 PM said...

A person essentially help to make seriously posts I would state. This is the very first time I frequented your website page and thus far? I amazed with the research you made to make this particular publish incredible. Great job! aircon installation

Unknown on July 4, 2018 at 9:02 PM said...

I came across your this post while trying to find information about blog-related research ... It's a good post .. keep posting and updating information.temperzone

Wania Sheikh on February 4, 2019 at 5:22 PM said...

Thanks for giving this information, Please do write more about Inverter Air Conditioner Price in Pakistan , Washing Machine Price in Pakistan & Water Dispenser Price in Pakistan

Unknown on December 28, 2020 at 4:54 PM said...

Error 111

daniel brain on April 5, 2021 at 1:54 PM said...

your article is helpful
visit our site
Thanks for sharing

ConnectHRMS on April 6, 2021 at 3:18 PM said...

Love all that you shared You describe all the things in detail. Your content is easy and understandable.
visit our site
Thanks for sharing

Connect-Sol on April 7, 2021 at 2:08 PM said...

Amazing article your work is great I learn too much from your blog. Your content is very helpful and informative
visit our site
Thanks for sharing

Unknown on April 28, 2021 at 4:46 AM said...

A good article saves this in your future. I hope that you are doing everything possible to allow yourself and make the future bright.
Buy Best Abayas in Pakistan

Ittefaq Electronics on September 13, 2021 at 1:30 PM said...

Amazing article your work is great i learn too much from this blog

Electro City on September 28, 2021 at 2:57 PM said...

I am extremely pleased to uncover this page. I wanted to thank you for your time just for this wonderful read !!online shoping

click link on November 5, 2021 at 2:21 PM said...

Thanks for sharing useful information ..... DiscountsPk has been facilitating the online consumer market and brand market

Winstore.pk on January 6, 2022 at 12:45 PM said...

Pakistan's premier online store with over 10,000 products at amazing discounts, available all across Pakistan with the options of Cash on Delivery (Cod), Check now

mobile on installment in lahore

Sana Saleem on March 1, 2022 at 4:26 PM said...

do you want to install Solar Tube Well system in Pakistan then you must check our website.

surmawala.pk on March 19, 2022 at 2:46 PM said...

well appreciate thanks for sharing it
air conditioner

Sherwin Currid Accountancy on April 2, 2022 at 6:22 PM said...

i read your blog its very informative you can also find best Chartered Accountant

Unknown on April 2, 2022 at 6:46 PM said...

I read your blog its is very informative find you can also find best finex digital services

Mansoor on April 18, 2022 at 1:57 AM said...

The best Gree Inverter AC of 2022 available at Aysonline. You can find them at lowest price. Get the amazing discounts.

Mrjack on April 25, 2022 at 2:22 PM said...

An amazing blog for us. It gives very emergent ideas to update designs. I'll be sure to read more blogs and get ideas about it and if you want to know about air conditioner prices then visit air conditioner price in Pakistan.

rays44 on April 25, 2022 at 3:34 PM said...

I must say one thing to the people that this content explores the complete information. Buy online led tv at low price in Pakistan Visit Us.

Mrjack on April 27, 2022 at 2:06 PM said...

I read your blog it's very informative and i want to know more about it but if you want to buy refrigerator or ac then go to 1.5 ton ac price for more details.

surmawala.pk on May 6, 2022 at 5:20 PM said...

what are the price bestair conditioner I review this blog I find useful information

surmawala.pk on May 6, 2022 at 5:21 PM said...

thanks for sharing it
air conditioner price in pakistan
haier air conditioner
ac price in pakistan
ac
inverter ac
inverter ac price in pakistan
ac
dc inverter ac
inverter ac
floor standing ac
gree
haier air conditioner

Mrjack on September 8, 2022 at 2:32 PM said...

This is an amazing blog you write i'm very impressed i also want to try to write like this on led tv price in pakistan.

Mrjack on October 6, 2022 at 2:42 PM said...

What an amazing article you write,also write an article on geyser price in pakistan i'm curious to read an blog on it.

Mrjack on October 7, 2022 at 4:43 PM said...

Very nice article and i'm really fond of reading like this type of blog and also contribute by writing on geyser price in pakistan.

Mrjack on October 8, 2022 at 1:55 PM said...

Very nice blog go to Al fatah for the sake of getting geyser price in pakistan in an appropriate budget.

Iqra Bashir on February 17, 2023 at 9:02 PM said...

R407C fault codes are diagnostic tools that help identify problems in air conditioning and refrigeration systems that use R407C refrigerant.

Fresh Music Marketing on April 11, 2023 at 3:04 PM said...

Thanks for sharing, please find the below links if you are looking for a best marketing company.

Facebook agency ad account
Facebook agency accounts

Radio Tv Centre on May 18, 2023 at 8:03 PM said...

you want to buy refrigerator or ac then go to price for more details.

Radio Tv Centre on May 18, 2023 at 8:10 PM said...

nice article for more information you can buy ac from

Harmonica Store on March 27, 2024 at 5:39 PM said...

thanks for sharing

Flower bouquet

Harmonica Store on March 27, 2024 at 6:01 PM said...

How to buy Flower bouquet

Post a Comment

 

| List of fault or error codes air conditioners © 2014. All Rights Reserved | Template Style by My Blogger Tricks .com | Design by Brian Gardner | Back To Top |